ATS Designers Guide 49
The ATS1801 interface has two RS232 ports that enable communications with a
computer and printer or a digital video recorder. The connection isn’t time-limited and the
connection security is ensured by a 10-digit security code that must be the same in the
control panel, and the PC to activate the connection.
3.3.3 Increasing the range between the control panel and PC.
Often the control panel is located a considerable distance from the PC on which the
system management program is running. Therefore the issue is vital for system design,
and it is necessary to predict what elements are required to connect the control panel to
the monitoring computer.
3.3.3.1 RS485
To increase the connection distance between the Advisor MASTER control panel, and
the PC with the managing software the system bus accessories can be used. By
converting the RS232 into RS485, we can achieve a maximum distance of 1500m. Bigger
distances can be achieved by following the steps described above in section 3.1.3
paragraph Increasing the system bus range
Table 3-17 Equipment list for remote RS485 connection.
Required
equipment
Description Amt.
ATS1801
Computer, printer interface (two RS232
ports) for the control panel
1
ATS1741 RS485 / RS232 bus converter 2
3.3.3.2 Modem and a dedicated leased line
Another solution is to use a leased phone line. Modems need to be installed on the
control panel and computer side of the line.
Table 3-18 Equipment necessary for remote modem connection
Required
equipment
Description Amt.
ATS1801
Computer, printer interface (two RS232
ports) for the control panel
1
MOD6000
External modem for communication with
ARITECH systems.
2
3.3.3.3 TCP/IP
By using RS232 – TCP/IP converters, the Ethernet network can be used to communicate
with the control panel. Although the bandwidth used by the Advisor MASTER system is
small the security system communications need to be made using separate wiring. This is
dictated by the need to protect the system from access by unauthorised persons.
Table 3-19 Equipment necessary for TCP/IP connection.
Required
equipment
Description Amt.
ATS1801
Computer, printer interface (two RS232
ports) for the control panel
1
ACA300 TCP/IP to RS232 converter 1