ATS Designers Guide 61
Table 4-6 DGP siren address map.
DGP Output Description
16 2, 15, 16
Control panel : Lamp, internal, external
Siren.
1 32 External siren
2 48
External siren
3 64
External siren
4 80
External siren
5 96
External siren
6 112
External siren
7 128
External siren
8 144
External siren
9 160
External siren
10 176
External siren
11 192
External siren
12 208
External siren
13 224
External siren
14 240
External siren
15 - Output 256 is not available
4.3 Areas
The control panels, depending on their type, have 4, 8 or 16 independent areas. Each
area can have independently set entry and exit times, internal and external sirens as well
as the beacon, reporting method etc. Common areas can be created in two ways:
connecting the areas or assigning zones from the common location to all areas. The area
linking mechanism is also used to create a cascade of vault areas. The areas linked with
the vault areas will be armed automatically once the vault areas are armed.
In systems where the number of independent areas exceeds 16, a network of control
panels needs to be used.
In cases when a large number of one-zone areas is necessary, for example, a shopping
mall with one zone for each shop, armed separately, the zone type 33 can be used – 24h
alarm and inhibit – which allows suspending of the zone using a keyswitch. This
application requires a different method of zone wiring. This way, it’s possible to achieve
up to 256 such security spots on one ATS4000 control panel.
4.4 Access control
The access control functions are available in the control panel. The RAS stations in the
control panel can control doors. Though access control implemented this way has some
limitations of the functions provided, it’s an affordable solution. It provides the basic
system functions for 16 doors at an attractive price. If the system requirements are
bigger, however, the ATS system can be equipped with a dedicated access control DGP,
implementing the advanced functions of such a system while at the same time staying an
integral part of the system. Four door – ATS1250 – and four lift – ATS1260 – modules are
available. They act as a DGP, and to a single control panel, up to 12 access control DGP
can be connected, which gives additional 48 doors per control panel. A detailed
description of configuring the access control functions of the control panel and the
ATS1250/60 DGP is provided in the following paragraphs.
The door, or elevator numbers are permanently assigned to the DGP addresses, a
detailed list can be found below.