ATS Designers Guide 37
default, after system memory restart, only the RAS number 1 is pooled. All RAS device
activity is saved in the system according to their number. The RAS station number also
defines the door number for central station based access control.
3.1.3 Bus topology
In accordance with the RS485 interface specification, the basic layout for the system bus
is a cascade connection of 32 devices. 16 RAS devices and 15 DGP devices can be
connected to the Advisor MASTER system data bus, which, along with the control panel,
gives 32 sending/receiving devices connected to the RS485 interface.
The bus configuration limits are imposed by the signal propagation in complex networks.
The signal “echoes” – a consequence of the signal bouncing in long network branches
due to different branches delay time – can cause multiple responses from one module,
which would be interpreted by the control panel as system sabotage. According to its
design, a system of class 3 and 4 should recognize and react to subsystem shutdown
attempts by switching devices. The echo effect can be mitigated through the use of
ATS174x bus expansion modules. The maximum bus length limits come from timing
dependencies of the device querying procedure. Any pooling errors or problems can be
read from the system menu, or through the diagnostic module of the TITAN software.
Each device connected to the ATS control panel has an inbuilt communication error
counter (max 255). That information can be used to test the bus configuration after
system installation.
3.1.3.1 Standard configurations
Because using only the cascade connection of system devices could be problematic,
some modifications of the cascade connection, as well as developing more complex
networks is permissible using the system bus accessories – the ATS174x devices.
1
2
3
32
. . . .
1500m
T
T
Drawing 3-4 Cascade connection
Standard data bus connections are the cascade connection and cascade connection with
branches up to 1500m. The control panel can be located in an arbitrary location in the
chain creating two branches. It has to be kept in mind that the total length of the bus
cannot exceed 1500m.